CAST-RE F-400
400º C/2h transmission extractor fan units in Magnelis sheet steel with maximum corrosion resistance according to ISO 12944
Fan:
• Structure in category C5 anti-corrosive Magnelis sheet steel.
• Backward curved impeller made of painted sheet steel.
• Glands for cable entry.
• Approved in accordance with standard EN 12101-3, with certificate no.: 0370-CPR-1578.
• Standardised set of pulleys, belts and guards in accordance with standard ISO-13857.
• Maximum temperature of air to be carried: -25 ºC +150 ºC.
Motor:
• Motors with IE3 efficiency for powers equal to or greater than 0.75 kW, except single-phase, 2-speed and 8-pole.
• Class F motors with ball bearings and IP55 protection.
• Three-phase 230/400 V 50 Hz (up to 4 kW) and 400/690 V 50 Hz (powers greater than 4 kW).
• Working temperature: -25 ºC +50 ºC.
Finish:
• Magnelis steel sheet.
On request:
• Different outlet positions.
• Circular outlet.